Using Dissolved Gas Analysis to Detect Active Faults in Oil-Insulated Electrical Equipment

Calendar
Duration:
11 min
calendar today
Published on
October 1, 2026
Featured Image

Dissolved gas analysis (DGA) detects active faults in oil-insulated electrical equipment by measuring the gases that form when insulating oil and paper break down under heat or electrical stress. Each fault type leaves its own gas signature. Arcing produces acetylene, overheating produces ethylene and methane, and partial discharge produces hydrogen.

Trending these gases over time tells you whether a transformer has a live problem, how severe it is, and how fast it is growing. That makes DGA the most widely used early-warning test for power transformers, reactors and tap changers. This guide covers the fault gases, the main interpretation methods, sampling schedules, and how to turn lab results into maintenance work.

Key Takeaways

  • Gas signatures: Each fault type releases a distinct mix of gases, so DGA can tell arcing, overheating and partial discharge apart without opening the tank.
  • Trends beat snapshots: The rate at which gases are generated is a stronger sign of an active fault than any single reading.
  • Several methods: Key Gas, Rogers Ratio and the Duval Triangle work best together to confirm a diagnosis.
  • Close the loop: DGA only prevents failures when an abnormal result creates a tracked work order with a clear owner and deadline.

What Is Dissolved Gas Analysis?

How dissolved gas analysis works: oil sample to gas chromatograph to ppm readings | Cryotos

Dissolved gas analysis is a lab or online test that measures fault gases in the insulating oil of electrical equipment to find and classify internal faults. A small oil sample is taken from the equipment while it is in service. A gas chromatograph then separates and measures each gas in parts per million (ppm).

DGA is a core condition monitoring technique for electrical assets because the oil touches every internal part of a transformer. It works much like a blood test: the sample shows what is happening inside without any shutdown or teardown.

The Standards That Guide DGA Programs

Two standards guide most dissolved gas analysis programs:

  • IEC 60599: The IEC 60599:2022 guidance on interpreting dissolved and free gases covers mineral oil-filled equipment and defines the fault classes most labs use.
  • IEEE C57.104-2019: The IEEE guide replaced older fixed limits with percentile-based gas levels and rate-of-change checks.
  • Asset management frameworks: ISO 55000 and RCM programs treat DGA as a key condition input for transformer risk and lifecycle decisions.

The core point is that DGA turns invisible chemical changes into measurable data you can trend and act on.

Equipment That Benefits from Dissolved Gas Analysis

Dissolved gas analysis applies to any electrical asset that uses oil as insulation and coolant. Power transformers are the main use case, but the same test protects several other asset types.

  • Power and distribution transformers: Step-up units, substation units and large plant transformers are the top DGA targets.
  • Shunt reactors: These run hot and continuously, so thermal faults show up early in the gas data.
  • On-load tap changers (OLTCs): Tap changers that switch in oil create some arcing gases normally, so they need their own baseline.
  • Oil-filled bushings and instrument transformers: Small oil volumes make faults show up fast, but sampling must follow the maker's guidance.
  • Oil-filled cables and switchgear: Some utilities also trend gases in these assets where sampling points exist.

Most facilities start with their biggest and most critical transformers. They add smaller units as the program grows. Start where a failure would cost the most.

How Faults Generate Gases in Insulating Oil

Four transformer fault types and the signature gases they release | Cryotos

A fault gas is a gas that forms when heat or electrical stress breaks down transformer oil or paper. Faults create these gases by breaking the chemical bonds in mineral oil and cellulose paper. The type of gas depends mostly on how much energy the fault releases and which material it attacks.

Thermal Faults from Hot Joints and Blocked Cooling

Overheating from loose connections, blocked cooling or stray flux breaks oil into methane and ethane at lower temperatures. As the hot spot gets hotter, ethylene takes over. Very hot faults can produce some acetylene as well.

Partial Discharge in Voids and Wet Insulation

Partial discharge is a low-energy electrical fault in gas voids or wet insulation. It mainly produces hydrogen with small amounts of methane.

Arcing Caused by High-Energy Electrical Breakdown

Arcing is the most dangerous fault in a transformer. It releases high energy and produces acetylene along with hydrogen. Acetylene only forms at very high temperatures, so any steady rise is a red flag.

Cellulose Breakdown in the Paper Insulation

When the paper insulation overheats, it releases carbon monoxide and carbon dioxide. Paper damage cannot be repaired, so these gases often decide the remaining life of the transformer.

Every fault type leaves a chemical fingerprint, and reading that fingerprint is the core skill of DGA.

Key Fault Gases Matrix for Dissolved Gas Analysis

Dissolved gas analysis tracks seven main fault gases plus oxygen and nitrogen. The matrix below links each gas to the fault it most often points to.

GasFormulaMain Fault IndicatedWhat It Tells You
HydrogenH₂Partial discharge, corona.Low-energy electrical stress; also rises with most other faults.
MethaneCH₄Low-temperature thermal fault.Oil heating below about 300°C, often with hydrogen.
EthaneC₂H₆Low to medium thermal fault.Oil overheating in the 300°C range.
EthyleneC₂H₄High-temperature thermal fault.Hot spots from about 300°C to over 700°C, such as poor joints or circulating currents.
AcetyleneC₂H₂Arcing, high-energy discharge.Even a few ppm can mean an active arc; the most urgent gas to trend.
Carbon monoxideCOCellulose (paper) overheating.Thermal stress on solid insulation.
Carbon dioxideCO₂Cellulose aging.Normal aging, or paper damage when read as a CO₂/CO ratio.

No gas tells the full story on its own, so labs read them together. A rise in hydrogen and acetylene together points to arcing, while hydrogen with only methane points to partial discharge.

Want to know what a transformer failure would cost your site? Try the unplanned downtime calculator to put a number on the risk.

DGA Interpretation Methods: Key Gas vs Rogers Ratio vs Duval Triangle

Four DGA interpretation methods: Key Gas, Rogers Ratio, Duval Triangle, Duval Pentagon | Cryotos

DGA interpretation methods turn raw gas readings into a likely fault type. Each method has strengths and blind spots, so experienced engineers use at least two.

MethodHow It WorksAdvantagesDisadvantages
Key Gas MethodLooks at which single gas dominates the total.Simple and quick for field screening.Less precise when two faults overlap.
Rogers Ratio MethodCompares CH₄/H₂, C₂H₂/C₂H₄ and C₂H₄/C₂H₆ ratios against coded ranges.Uses ratios, so results do not depend on oil volume.Some gas patterns return no diagnosis.
Duval TrianglePlots relative CH₄, C₂H₄ and C₂H₂ percentages into fault zones.Always gives a diagnosis; widely used with IEC 60599.Needs gases above detection limits to be reliable.
Duval PentagonPlots five gases: H₂, CH₄, C₂H₆, C₂H₄ and C₂H₂.Helps resolve unclear or mixed-fault cases.More complex; usually needs software.

The Duval Triangle is the most common choice today because it always places a sample in a fault zone. Its zones cover partial discharge (PD), low and high energy discharges (D1, D2), and thermal faults at three temperature levels (T1, T2, T3). The dissolved gas analysis overview on Wikipedia shows how the Key Gas, Rogers Ratio, Duval Triangle and Duval Pentagon methods relate.

Use one method to screen, and a second to confirm before you plan an outage.

How Dissolved Gas Analysis Separates Active Faults from Old Gassing

Four-step DGA fault confirmation ladder: Detect, Trend, Classify, Act | Cryotos

Dissolved gas analysis separates active faults from old gassing by comparing gas levels across several samples over time. A high reading can be left over from a fault that stopped years ago. A rising reading means the fault is still active.

An active fault is a fault that is still generating gas at a measurable rate between samples. The generation rate, usually expressed in ppm per day or per month, is the clearest sign of one.

The Four-Step DGA Fault Confirmation Ladder:

  • Detect: Flag any gas above your typical level or any new acetylene reading in the latest sample.
  • Trend: Resample within days to weeks and calculate the generation rate for each gas.
  • Classify: Run the gases through the Duval Triangle and Rogers Ratio to name the likely fault type.
  • Act: Match the response to the fault severity and the asset's criticality, from closer monitoring to a planned outage.

Common Mistakes When Trending DGA Results

  • Acting on one sample: Contaminated syringes, air bubbles or a recent oil top-up can skew a single result.
  • Ignoring oil processing history: Degassing or filtering resets gas levels, so the trend must restart from that date.
  • Treating tap changer gases as main tank faults: A leaking OLTC barrier can pass normal switching gases into the main tank.

The US Bureau of Reclamation transformer maintenance guide (FIST 3-30) also bases its action levels on total combustible gas and monthly generation rates, not single readings. The rate of change is what turns a number into a decision.

DGA Sampling Schedule and Online Monitoring

A DGA sampling schedule should follow how critical the asset is and how it is running now. A fixed calendar alone is not enough. Healthy units need less frequent checks, while a unit with rising gases needs much closer watch.

Asset ConditionSampling IntervalMethodEscalation Trigger
Healthy, non-critical transformerEvery 12 monthsLab DGA.Any gas above typical levels or a new acetylene reading.
Healthy, critical transformer (GSU, main substation)Every 3–6 monthsLab DGA plus online monitor.Rate of change above your baseline trend.
Caution: one or more gases risingMonthly to quarterlyLab DGA, confirm with resample.Generation rate keeps rising across two samples.
Active fault suspectedWeekly or continuousOnline multi-gas monitor.Acetylene increase or a sudden rise in total combustible gas.

Online DGA monitoring is a sensor system fixed to the transformer that measures dissolved gases every few hours without manual sampling. It sends alarms on fast changes. Online monitors suit critical units and transformers already showing a fault, where waiting weeks for a lab result is too risky.

Connect online monitors to your maintenance system through IoT integration so readings and alarms create tasks automatically. Match the sampling interval to the risk, and tighten it the moment a trend starts climbing.

Turning DGA Results into Maintenance Action

DGA results only stop failures when each bad result becomes a tracked task. Many maintenance teams still receive lab reports by email, file them, and act weeks later.

Build a Clear Response Path for Every Result

  • Normal result: Record it against the asset and keep the routine interval.
  • Caution result: Create a resample task with a due date and a named owner.
  • Active fault confirmed: Raise an inspection work order, check load and cooling, and plan an outage if gases keep rising.
  • Critical result: Follow your switching and isolation procedure and prepare spares or a mobile transformer.

Store every DGA report on the asset record in a Computerized Maintenance Management System, so the trend history is one click away during a review. Linking results to work order management makes sure no flagged sample goes unanswered.

Maintenance teams using Cryotos have reported up to 30% reduction in unplanned downtime and 25% faster repair turnaround after linking condition data to structured work orders. Utilities and generating sites can also use dedicated power plant maintenance software to plan transformer outages around generation schedules. The fastest DGA program is the one where every red flag has an owner within hours.

Frequently Asked Questions

How often should I run dissolved gas analysis on a power transformer?

Most utilities test healthy transformers once a year and critical units every three to six months. If any gas starts rising, shorten the interval to monthly or weekly, or install an online monitor until the trend is understood.

Which gas in a DGA report is the most serious warning sign?

Acetylene is the most serious warning sign because it forms only at the very high temperatures of an electrical arc. Any new or rising acetylene reading in a main tank should trigger a resample and an engineering review right away.

Can dissolved gas analysis tell me exactly where a fault is inside the transformer?

No, DGA tells you the type and severity of a fault, not its exact location. Engineers combine DGA with electrical tests, infrared scans and load data to narrow down where the fault sits before opening the unit.

What is the difference between lab DGA and online DGA monitoring?

Lab DGA uses a sampled syringe of oil that is tested in a laboratory, giving high accuracy at set intervals. Online DGA monitors sit on the transformer and measure gases every few hours, so they catch fast-developing faults that a yearly lab test would miss.

Does a high gas level always mean my transformer is about to fail?

Not always, because gases can remain from an old fault that is no longer active. The key question is whether the gas level is still rising between samples, which shows an active fault that needs action.

Dissolved gas analysis gives you weeks or months of warning before an oil-insulated asset fails, but only if every result reaches the right person. Schedule a free demo to see how Cryotos turns DGA findings into tracked work orders, trend history and planned outages.

Want to Try Cryotos CMMS Today?

Get Free Demo

Let AI Take Control of Your Maintenance

Cryotos AI predicts failures, automates work orders, and simplifies maintenance—before problems slow you down.

Try AI-Powered CMMS
🡢